Safety StandardsLimited

EICR codes explained: C1, C2, C3 and FI

Every defect on an EICR is given a code. Here is what each one means, which codes make a report unsatisfactory, and what you need to do.

The four EICR codes at a glance

CodeMeaningReport resultAction
C1Danger present, risk of injuryUnsatisfactoryImmediate. Usually made safe on the day.
C2Potentially dangerousUnsatisfactoryUrgent. Within 28 days for landlords, or sooner.
FIFurther investigation required without delayUnsatisfactoryInvestigate within 28 days for landlords, or sooner.
C3Improvement recommendedStill satisfactoryRecommended, not mandatory.

C1: Danger present

A C1 means there is an immediate risk of electric shock or fire. The inspector should make the danger safe straight away, for example by isolating the circuit, and tell you in writing.

Common examples: exposed live conductors, a broken socket with live parts accessible, incorrect polarity, or burnt and damaged equipment that is in use.

C2: Potentially dangerous

A C2 means the installation could become dangerous if a fault happens or conditions change. It requires urgent remedial action.

Common examples: no main protective bonding to the gas or water pipes, inadequate earthing, sockets likely to supply equipment outdoors without RCD protection, or a consumer unit with signs of overheating.

FI: Further investigation required

FI means the inspector found something that needs more investigation, but could not confirm the cause during the inspection. It must be investigated without delay, because it may reveal a C1 or C2 defect.

Common examples: a circuit that could not be traced, unexpected test results, or a suspected hidden fault.

C3: Improvement recommended

A C3 means the installation does not meet the current edition of BS 7671 but is not dangerous. A report with only C3 observations can still be satisfactory. Improvements are recommended, and are often worth doing when you carry out other work.

Common examples: an older consumer unit without RCD protection on some circuits where it is not considered dangerous, or missing labels and circuit charts.

What to do if your EICR has C1, C2 or FI codes

  1. Act on any C1 straight away. The circuit should already have been made safe.
  2. Get a quote for remedial work on every C2 and FI. You can send us your report and we reply within a few hours.
  3. Complete the work within 28 days, or sooner if the report says so.
  4. Keep the paperwork and give written confirmation to tenants and the local authority within 28 days of completion.

Frequently asked questions

Does a C3 fail an EICR?

No. C3 means improvement recommended. A report with only C3 observations can still be satisfactory.

Which EICR codes make a report unsatisfactory?

Any C1, C2 or FI observation makes the overall EICR unsatisfactory.

How long do landlords have to fix C2 items?

In England, remedial work must be completed within 28 days of the inspection, or within any shorter period stated in the report.

Last reviewed: By the Safety Standards Ltd. compliance team

This guide is general information for UK landlords and property owners, not legal advice. Rules differ between England, Wales, Scotland and Northern Ireland and can change, so check current government guidance for your property.

Book your certificate online

Choose a service, get your job number straight away and track every stage online. Certificates are emailed within 24 hours.